1
2
3
THE DISPLACEMENT CURVEPERFORMING THE MEASUREMENTDISPLACEMENT TRANSDUCERS INSTALLATION EXAMPLES

1.1 Description
1.2 Operation on opening
1.2.1 Zone A : the beginning of the movement
1.2.2 Zone B : contact separation
1.2.3 Zone C : deceleration
1.3 Operation on closing
1.3.1 Zone A : the beginning of the movement
1.3.2 Zone B : contact closing
1.3.3 Zone C : deceleration
1.4 Velocity curve
1.5 Acceleration curve

2.1 Displacement transducer
2.1.1 Description
2.1.2 Operation
2.2 Circuit Breaker
2.2.1 Description
2.2.2 Electrical power section
2.2.3 Command section
2.3 Choice of transducers
2.4 Acquisition and display of results
2.5 Displacement curve
2.5.1 Velocity
2.5.2 Instantaneous velocity curves
2.5.3 Average velocity
2.5.4 Average velocity calculation example for OPEN operation
2.5.5 Average velocity calculation example for CLOSE operation
2.5.6 GENERAL PRECAUTIONS

EXAMPLE 1 : ABB BREAKER
EXAMPLE 2 : AREVA GL BREAKER
EXAMPLE 3 : SPRING TYPE BREAKER
EXAMPLE 4 : T-TYPE BREAKER
EXAMPLE 5 : GE BREAKER
EXAMPLE 6 : BULK OIL BREAKER
EXAMPLE 7 : HPL BREAKER
EXAMPLE 8 : HPL T-TYPE BREAKER (BLG mechanism)
EXAMPLE 9 : GFX BREAKER
EXAMPLE 10 : GL T-TYPE BREAKER
EXAMPLE 11 : ABB BREAKER
EXAMPLE 12 : MAGNE BLAST BREAKER
EXAMPLE 13 : MOUNTING EXAMPLE WITH A MAGNETIC BASE
EXAMPLE 14 : CROMPTON GREAVES BEAKER
EXAMPLE 15 : HGF DEAD TANK BREAKER BY AREVA

 

1
THE DISPLACEMENT CURVE

 1.1 DESCRIPTION

During circuit breaker timing tests, the measurement of the operation times from the first appearance of the order on the command coil to the switching of the main contact, is recorded with a timing instrument, such as the ZENSOL CBA-32P.

This measurement offers precious information on the state of the circuit breaker and allows, in most cases, the precise verification of the presence or absence of anomalies. But this information does not reveal all the secrets of the circuit breaker. Other important information remains hidden from view.

Whenever it is possible, a point-by-point measurement of the movement of the internal components of the circuit breaker, from the beginning of the movement until it comes to a complete stop, traces a curve called a DISPLACEMENT CURVE.

While the main contact timing curve gives the moment when the movement starts and the moment when the contact switches over, the information contained in the displacement curve is interesting because it allows us to follow the entire movement from beginning to end.

 1.2 OPERATION ON OPENING

An example of a displacement curve for an Open operation is shown in Fig. 1.2, superimposed on an opening timing curve for the main contact (in red).

Figure 1.2 – Displacement curve on Open operation

Even of the general shape of the curve is the first characteristic to check, three Zones (circled in Fig. 1.2) merit particular attention.

1. Zone A : the beginning of the movement
2. Zone B : contact separation
3. Zone C : from the beginning of the deceleration to the final resting position

 1.2.1 ZONE A : THE BEGINNING OF THE MOVEMENT

This is where the movement starts. It is extremely important to know if the movement has begun at the right moment. For example, a delay with respect to the reference specification means an electrical problem exists, if the coil is not excited on time, or a mechanical problem may exist between the command mechanism where the movement is triggered and the mobile contact of the breaker itself.

 1.2.2 ZONE B : CONTACT SEPARATION

This is where the main contacts separate from each other. A this exact instant, the arc begins to form and the breaker implements its measures to extinguish it. The separation speed becomes an important and primordial factor in order to succeed in breaking the circuit.

The method for calculating the average velocity in this zone depends on the breaker designer. Only the designer may determine the calculation method and establish the reference specification.

 1.2.3 ZONE C : DECELERATION

This is where the movement decelerates until the circuit breaker’s mobile contact comes to a complete stop.

The amount of energy required in the breaking process is proportional to the intensity of the current being interrupted. Once the current has been interrupted and the arc has been extinguished, the energy developed is quite excessive.

Effective means of damping are put into action to absorb this excess energy and thus reduce the risk of damaging the internal components of the circuit breaker. The analysis of this zone makes it possible to determine if the damping is optimal, which means the movement is stopped gradually.

Insufficient damping, or underdamping, allows the moving parts to undergo shocks at the end of the travel, which causes severe damage.

A sudden damping, where the kinetic energy developed by the moving parts of the breaker is absorbed over very little time, causes damage similar to underdamping. This phenomenon is called overdamping.

 1.3 OPERATION ON CLOSING

An example of a displacement curve for a Close operation is shown in Fig. 1.3, superimposed on a timing curve for the main contact (in red).

Displacement curve for Close operation

Figure 1.3 – Displacement curve for Close operation

Even of the general shape of the curve is the first characteristic to check, three Zones (circled in Fig. 1.3 merit particular attention.

1. Zone A : the beginning of the movement
2. Zone B : contact closing
3. Zone C : from the beginning of the deceleration to the final resting position

 1.3.1 ZONE A : THE BEGINNING OF THE MOVEMENT

As is the case for the opening displacement curve, this is where the movement starts, and it is very important to know if the movement started at the right place.

 1.3.2  ZONE B : CONTACT CLOSING

This is where the main contacts come into contact. In this zone, also called the pre-arc zone, as the contacts come closer to each other, the dielectric, as a function of the separation distance, becomes insufficient and a pre-arc current forms within an arc, the duration of which is a function of the speed of the contacts.

Thus, contact velocity is an important factor in limiting premature wear of the contacts.

As is the case for the opening operation, the method for calculating the average speed in this zone is also determined by the designer of the breaker. Only the designer may determine this calculation method and establish the reference specification.

 1.3.3  ZONE C : DECELERATION

This is where the movement slows down to a complete stop of the breaker’s mobile contacts.

The energy involved in the closing process is less than that developed in the breaking process, but it is nonetheless quite considerable.

Excess energy is translated into an overtravel which, if it exceeds tolerances, may cause severe damage to the device.

 1.4 VELOCITY CURVE

A velocity curve is calculated by the derivative of the displacement curve, using the CBA Win analysis software, for example. The velocity curves gives the speed as a function of time, which gains new information on the dynamic behavior of the circuit breaker.

 1.5 ACCELERATION CURVE

In the same manner, an acceleration curve can be traced, as the derivative of the velocity curve, again using the CBA Win analysis software, which gives us more useful data.
1
PERFORMING THE MEASUREMENT
To record the displacement curve, some kind of assembly is needed between the ZENSOL CBA32P and the breaker. A displacement transducer is used to sense the movement of the mobile contact. The CBA Win software processes the data, traces the displacement curve and performs the various velocity calculations. To understand the process, a summary description of the transducer, of the breaker and the CBA-32P follows.

 2.1 DISPLACEMENT TRANSDUCER

 2.1.1 DESCRIPTION

The displacement transducer, in its most elementary form, consists of a fixed part and a mobile part. The mobile part is attached to the mobile contact of the breaker under test, and moves with the contacts, while the fixed part acts as a reference.

Several types of transducers are available on the market. Their differences reside in the method used to identify the relative value against the reference value. Some examples of transducers are:

– Magnetic transducer
Optical transducer
Resistive transducer
– etcétera.

The resistive transducer, which is the most popular, will be described in detail. This type of transducer is composed of a resistor and a cursor that moves along the length of this resistor. There are two types of resistive transducers:

– Linear displacement transducer, or linear transducer (Fig. 2.11a)
– Rotary displacement transducer, or rotary transducer (Fig. 2.11b)

The difference lies in the physical layout of the reference resistor and in the way the cursor moves.

Figure 2.11a – Linear displacement transducer

For the linear transducer, the displacement of the cursor is linear, in a straight line, whereas for the rotary transducer the displacement is a rotation around an axis.

Figure 2.11b – Rotary displacement transducer

 2.1.2 OPERATION

The transducer is solidly attached to the breaker support, while the mobile cursor is solidly attached to the control arm of the mobile contac.

A known, fixed voltage source (E) is connected to terminals (1) and (3). When the breaker is in the CLOSED position, the voltage read between terminals (2) and (3) is (V1). As the mobile contact moves toward the OPEN position, the measured voltage (Vt) between terminals (2) and (3) decreased as a function of time, down to value (V2), which is less than (V1), when the breaker has completely stopped.

Figure 2.1.2 Operation of a displacement transducer

 2.2 CIRCUIT BREAKER

 2.2.1 DESCRIPTION

A high-voltage circuit breaker consists of two main parts:

1. Active section (electrical power)
2. Command section

The active section must make or break the power current in the high-voltage circuit where the breaker is installed. The command section must develop the necessary energy to perform these operations.

The link between the command and active sections is usually an insulating rod, shown in red in the schematic in Figure 2.2.1.

Figure 2.2.1 Circuit breaker principle

 2.2.2 ELECTRICAL POWER SECTION

This part is generally constituted of three phases of equal size. Each phase in turn is composed of a fixed contact assembly and a mobile contact assembly. When the two assemblies are in contact, it is said that the breaker is CLOSED, so current flows through the power circuit.

To interrupt the flow of current in the power circuit, the mobile contact assembly is mechanically moved away from the fixed contact assembly and stopped at a distance that is sufficient to ensure electrical isolation.

Figure 2.2.2 – Power section of the circuit breaker

 2.2.3 COMMAND SECTION

This section has the task of creating the energy required to perform the mechanical operation of the breaker, for both Open and Close operations.

Three types of commands are often used in high-voltage circuit breakers:

– Pneumatic
– Hydraulic
– Mechanical spring

 2.2.3.1 PNEUMATIC COMMAND

Usually found on compressed air circuit breakers. This type uses compressed air as a dielectric medium and uses piston-type mobile contacts.

A series of valves activated in a precise sequence allows the application of air pressure on one side of the piston, which causes the latter to move through the action of the pressure difference between the opposing sides of the piston. The movement of the mobile contacts is generally not accessible in this type of circuit breaker, making the use of conventional transducers almost impossible.

 2.2.3.2 HYDRAULIC COMMAND

Figure 2.2.32 – Hydraulic command

 2.2.3.3 SPRING-LOADED MECHANICAL COMMAND

This type is most in demand because of its proven reliability and also because of its very low frequency of periodic maintenance.

It usually consists of two compressed springs, one used to accumulate the energy necessary to close the breaker and the other to store energy to open the breaker.

The closing spring (E) is compressed manually, using a crank, or electrically, using a motor. A locking mechanism holds and controls the energy accumulated in the closing spring.

When this energy is released, by the release of the closing spring, the mobile contact is moved toward the fixed contact, through the connecting rods, while simultaneously charging the opening spring which maintains the energy accumulated with its own locking mechanism, ready to be released on the next opening order.

Figure 2.2.33 – Mechanical spring command

 2.3 CHOICE OF TRANSDUCERS

The goal is to reproduce the exact movement of the moving contact in the breaking chamber of the circuit breaker, which is usually inaccessible because the entire assembly is inside a closed container. While the final displacement of this mobile contact is always linear, the initial movement generated by the command mechanism is not always so.

The movement generated by the command mechanism may be rotary, which is translated into a linear motion by a set of levers and connecting rods.

When the linear movement of the contact is accessible indirectly, for example through the connecting rod, a linear transducer may accurately reproduce this movement by attaching it to the rod in question. In figure 2.3a, you will find an example of a linear motion sensed by a linear transducer (in the case of an accessible motion).

Figure 2.3a – Linear transducer examples

In the case where only the command motion is accessible, and if this motion is rotary, the final motion of the mobile contact is measured by transforming this rotary motion using various levers and connecting rods of different sizes.

The sizes of the levers add multiplying factors that influence the desired curve, whereas the angular motion of these levers is always the same. In this case, using rotary transducers will give better results.

One condition must be observed, however. A translation curve must be drawn, point-by-point, to convert the angular motion into a linear one.

An example of the use of a rotary transducer is shown in figure 2.3b.

Figure 2.3b – Example using rotary transducers

 2.4 ACQUISITION AND DISPLAY OF RESULTS

The acquisition and the display of the results is performed by the analog input channels of ZENSOL’s CBA-32P (see Fig. 2.4a).

Each analog channel has three leads numbered (1), (2), and (3) on the corresponding plug.

Between leads (1) and (3), a 10 volt DC signal is generated during the test.. The signal collected from the displacement transducer is measured between (2) and (3), and transmitted to the CBA Win analysis software, which draws the curve on the computer screen.

Figure 2.4b shows an example of CBA Win’s graphic report, as it is shown on the computer screen.

Figure 2.4a – Zensol CBA-32P instrument

Figure 2.4b – CBA Win© graphic report as seen on the computer screen

 2.5 DISPLACEMENT CURVE

The displacement curve is generally drawn with the unit of measurement (millimeters – mm) on the vertical axis and the time in milliseconds on the horizontal axis. Figure 2.5 shows examples of displacement curves for Close and Open operations.

Figure 2.5 – Examples of displacement curves for Close and Open operations

 2.5.1 VELOCITY

The speed of the contacts on opening, as on closing, is an important parameter in the operation of high-voltage circuit breakers. The displacement curve also serves to the calculate the speed of the contacts at a specific moment, or instantaneous velocity, or it may serve to calculate the average speed for a predetermined time interval, or average velocity.

 2.5.2 INSTANTANEOUS VELOCITY CURVES

The CBA Win software draws a curve of the instantaneous velocities, calculated by deriving the data in the displacement curve. Below is an example of the derivation of a displacement signal (in green) that produced a curve showing the evolution of the displacement velocity (in orange).

 2.5.3 AVERAGE VELOCITY

The velocity usually sought is at the moment the breaker contacts make (on Close) or break (on Open). However, since it is difficult to obtain a consistent speed for each operation, it is better to calculate an average speed over a time interval extending before and after this point.

The exact calculation method must be obtained from the circuit breaker’s manufacturer, so the measured values may be compared to the reference specification of the manufacturer.

 2.5.4 AVERAGE VELOCITY CALCULATION EXAMPLE FOR OPEN OPERATION

To calculate the average speed on Opening, point A on the displacement curve, which is the exact moment the main contacts separate, must be determined. Point B is determined by adding dT milliseconds (ms) to the time of Point A.

Average velocity calculation example for OPEN operation

Displacement axis value of point A = YA mm
Time axis value of point A = XA ms
Displacement axis value of point B = YB mm
Time axis value of point B = XB ms

The average velocity on Opening, in meters per second (m/s), is calculated using the following formula:

 

In this case XB-XA = dT = 100 ms
YA-YB = dY = 223.71 mm, so:

 

 2.5.5 AVERAGE VELOCITY CALCULATION EXAMPLE FOR CLOSE OPERATION

To calculate the average velocity for a Close operation, point A on the displacement curve, which is the exact moment the main contacts make contact, must be determined. Point B is found by subtracting dT milliseconds (ms) from the time of point A.

Displacement axis value of Point A = YA mm
Time axis value of Point A = XA ms
Displacement axis value of Point B = YB mm
Time axis value of Point B = XB ms

The average velocity on Closing, in meters per second (m/s), is calculated using the following formula:

In this case XA-XB = dT = 100 ms
YA-YB = dY = 240.5 mm, so:

 

 2.5.6 GENERAL PRECAUTIONS

Certain precautions are to be observed when the transducer is installed and the cables are connected:

 2.5.6.1 CURVAS INVERTIDAS

In general, displacement curves show the CLOSED position higher than the OPEN position. To observe this rule, the wires must not be interchanged between terminals 2 and 3 of the transducer. otherwise the curve will be draw upside down (see figures 2.5.6a and b).

Figure 2.6.1a – Connections causing an inverted displacement curve

Inverted displacement curve example
Figure 2.6.1b – Inverted displacement curve example (Close)

 2.5.6.2 TRANSDUCER CAPACITY

When the transducer is installed, it must be ensured that the motion measured does not exceed the capacity of the transducer or it will be damaged, and the curve shown will not represent the true motion of the circuit breaker. In the following graphic is an example of what happens when the transducer « bottoms out » before the breaker attains the end of its movement, as seen by the sharp angle at the bottom of the graphic.

 

Fig. 2.6.2 – Example of a displacement curve exceeding a transducer’s range