Universal Recloser Control Analyzer - GEN_I3V
The GEN-I3V is a universal recloser analyzer designed to test all types of recloser controls. It is designed to replace all old electronic recloser control testers. In addition to current injection it can inject 3 different voltages.
Connected to the appropriate interfaces (COOP-BOX, ABB-BOX, WEST-BOX), the GEN-I3V can test: Mc Graw-Edison, Cooper reclosers type F3, F4, F5, FXB, DC NOVA, as well as the ESV Westinghouse, Joslyn 351J, ABB PCD2000, Schweitzer SEL-351R or any equivalent.
The I3v is driven by a very powerful software, OpenZen I3V.
OpenZen I3V software is supplied with the equipment and all the upgrades are free.
Connected to the appropriate interfaces (COOP-BOX, ABB-BOX, WEST-BOX), the GEN-I3V can test: Mc Graw-Edison, Cooper reclosers type F3, F4, F5, FXB, DC NOVA, as well as the ESV Westinghouse, Joslyn 351J, ABB PCD2000, Schweitzer SEL-351R or any equivalent.
The I3v is driven by a very powerful software, OpenZen I3V.
OpenZen I3V software is supplied with the equipment and all the upgrades are free.
Main advantages
Hardware
OpenZen I3V:
- Direct replacement of the K-MET universal analyzer that can test all types of recloser controls
- Direct connections to all recloser controls via interfaces
- Insensitive to noise and high voltage transients
- USB communication link
OpenZen I3V:
- Automated tests reports
- Full control over current injection and voltage forms
- Automatic point positioning on graphics
- Simulate various faults of power lines
- Minimum Trip detection
- Reclosing interval measurement
- Reset time (Rearm delay)
Technical description
Hardware
Software
- 1 current output (software programmable by frequency, phase and amplitude)
* Amplitude of the Injected Current : 14 amp RMS by step of 4 mA
* Frequency Range : 0 to 10 kHz
* Frequency resolution : 0.004 Hz
* Phase shift: 0 to 360 degrees by steps of 0.09 degrees - 3 voltage outputs (software programmable individually in frequency, phase and amplitude)
* Voltage range: 0 to 200V peak to peak by step of 50 mV peak
* Signal forms: sinusoidal, triangular, square or DC
* Frequency Range : 0 to 10 kHz
* Frequency resolution: 0.004 Hz
* Phase shift : 0 to 360 degrees by steps of 0.09 degrees - USB high speed link
- Amphenol connector
Software
- Signal form controlled and set by software
- Recording length : 1 millisecond to 17 minutes.
- Sampling time : 6 microsecond to 32 000 microsecond
- Comply to international standards ANSI C-37-60 and IEEE Std 321-1973
Commercial references
Product reference : GEN_I3V
Accessories included with the instrument
- OpenZen I3V softwareŠ
- User's guide
- USB cable
- 1 day training
- Power cord
Specialized Interfaces
Optional accessories
Sharing Knowledge
| Precision Recloser Testing | 0.7 MB | 16 Jun. 06 |
|
|
* Specifications and appearance may change without notice