Universal Recloser Control Analyzer - GEN_I3V

The GEN-I3V is a universal recloser analyzer designed to test all types of recloser controls. It is designed to replace all old electronic recloser control testers. In addition to current injection it can inject 3 different voltages.

Connected to the appropriate interfaces (COOP-BOX, ABB-BOX, WEST-BOX), the GEN-I3V can test: Mc Graw-Edison, Cooper reclosers type F3, F4, F5, FXB, DC NOVA, as well as the ESV Westinghouse, Joslyn 351J, ABB PCD2000, Schweitzer SEL-351R or any equivalent.

The I3v is driven by a very powerful software, OpenZen I3V.

OpenZen I3V software is supplied with the equipment and all the upgrades are free.

Main advantages

Hardware
  • Direct replacement of the K-MET universal analyzer that can test all types of recloser controls
  • Direct connections to all recloser controls via interfaces
  • Insensitive to noise and high voltage transients
  • USB communication link

OpenZen I3V:
  • Automated tests reports
  • Full control over current injection and voltage forms
  • Automatic point positioning on graphics
  • Simulate various faults of power lines
  • Minimum Trip detection
  • Reclosing interval measurement
  • Reset time (Rearm delay)

Technical description

Hardware
  • 1 current output (software programmable by frequency, phase and amplitude)
      * Amplitude of the Injected Current : 14 amp RMS by step of 4 mA
      * Frequency Range : 0 to 10 kHz
      * Frequency resolution : 0.004 Hz
      * Phase shift: 0 to 360 degrees by steps of 0.09 degrees
  • 3 voltage outputs (software programmable individually in frequency, phase and amplitude)
      * Voltage range: 0 to 200V peak to peak by step of 50 mV peak
      * Signal forms: sinusoidal, triangular, square or DC
      * Frequency Range : 0 to 10 kHz
      * Frequency resolution: 0.004 Hz
      * Phase shift : 0 to 360 degrees by steps of 0.09 degrees
  • USB high speed link
  • Amphenol connector

Software
  • Signal form controlled and set by software
  • Recording length : 1 millisecond to 17 minutes.
  • Sampling time : 6 microsecond to 32 000 microsecond
  • Comply to international standards ANSI C-37-60 and IEEE Std 321-1973

Commercial references

Product reference : GEN_I3V
Accessories included with the instrument
  • OpenZen I3V softwareŠ
  • User's guide
  • USB cable
  • 1 day training
  • Power cord

Sharing Knowledge

Precision Recloser Testing 0.7 MB 16 Jun. 06
 
* Specifications and appearance may change without notice