french
 
 
 
The circuit breaker test instrument specialist The recloser test instrument specialist The tap changing test instrument specialist Major line of Zensol products A wide range of accessories

Featured products

HV Circuit Breaker Vibration Analyzer - CBV-19

Zensol is the first to introduce a new instrument, the CBV-19, totally dedicated to vibration measurements on HV circuit breakers.
This new instrument will allow the maintenance crew to detect mechanical anomalies in the circuit-breaker drive mechanisms and other moving parts in the interrupting chamber that should be inspected and overhauled.

The CBV-19 is used in conjunction with accelerometers. Its high sampling frequency of at least 150 kHz allows to catch a large variety of mechanical anomalies.

The CBV-19 comes with powerful and user-friendly software : OpenZen - CBV for analyzing the defect severity and plan further maintenance actions. It integrates many calculation functions including: noise suppression, amplitude and time deviations between measured and reference signals, frequency spectrogram depicting relevant frequencies.

Main advantages

  • Easy detection of mechanical anomalies
  • Extensive calculation functions including noise suppression, amplitude, etc.
  • Possibility to create test plans
  • Control over the close and open commands of the circuit breaker
  • Robust and portable
  • For use in High Voltage environment
  • Can be used on any type of breakers
  • Easy installation

Sharing Knowledge

Improved Vibration Analysis on CBs 3.2 MB 08 Oct. 08
Article published on "IEEE Transactions on Power Delivery", Vol. 23, No. 4, October 2008
 

Technical description

  • 16 analog channels including:
        12 BNC inputs (-10 to +10V)
        2 current inputs (-20 to +20A)
        1 neutrik inputs (0 to 10V)
        1 contact input (for close/open monitoring)
  • Sampling frequency :
        150 kHz for 8 channels
        300 kHz for 1 channel
  • Sampling time:
        3us for 1 channel
        6us for 8 channels
  • Recording time :
        1ms to 60 minutes for 8 channels
        1ms to 7 hours for 1 channel
  • Data acquisition system with 16 bit resolution for A/D conversion

Commercial references

Product reference : CBV-19
Accessories included with the instrument
  • OpenZen - CBV operating software
  • USB to fiber optic module
  • Shielded cables for the the accelerometers and the coil command
  • Manual
  • 1 day training at Zensol's premises (travel expenses of the attendees not included).
Optional accessories
  • Mechanical bases for the accelerometers
  • Calibration tools (vibration).
  • Piezo-electrical type Accelerometers
  • Insulated accelerometers
  • Laptop computer
  • ICP 4 inputs conditioner
  • BNC-BNC cables (5' to 50')
  • BNC to 1032 cable (3')
  • Contact cable 10'
  • Contact/displacement extension cable (50')
  • Carrying case
CBV-19
CBV-19
* Specifications and appearance may change without notice
CBV Visual Overview 390.3 KB 17 Aug. 11
Brochure 2.0 MB 26 Jan. 12