CBA-32P Specifications
|
HARDWARE SPECIFICATIONS |
| GENERAL SPECIFICATIONS |
| TRUE computerized circuit breaker analyzer The software initiates the commands. No external manipulation (switch or button) required to initiate the command. No test plan transfer to the unit required before test. |
| No built-in LCD screen |
| No built-in thermal printer. |
| No built-in keyboard. The units are controlled by the CBA WIN™ software through any standard PC computer. The CBA WIN™ software is supplied with the unit at no extra charge. |
| Insensitive to noise and high voltage transient in high voltage substation environments up to 800,000 volts |
| DIGITAL INPUTS/CONTACT INPUTS |
| Number of digital contacts available: 3, 8, 16, 24 contacts |
| Each contact can detect simultaneously the main contact AND the resistive contacts. No manual switch on the unit to switch to resistive. |
| Maximum number of main contacts: 24 |
| Maximum number of resistive contacts: 24 |
| Can operate all types of breakers up to 8 breaks per phase with resistances at Close and Open. |
| Each cable handles 2 contacts. 4 cables -> 8 contacts 8 cables ->16 contacts 12 cables -> 24 contacts |
| ANALOG INPUTS (OPEN HARDWARE ARCHITECTURE) |
| 5 or 8 Analog inputs 12 bits A/D converter Universal Analog input range : 0 to 10VDC |
| 2 built-in current sensors (one for close current, one for open current AC/DC) |
| 3 or 6 general purpose ANALOG inputs (user-configurable) configurable as voltage, current, pressure, displacement, temperature, etc. working exactly like a multi-channel storage oscilloscope. |
| Ability to use the equipment as a multi-channel storage oscilloscope. |
| No calibration of the transducers required before use |
| MEASUREMENTS |
| User-configurable sampling times : 32 microseconds to 32,000 microseconds! |
| User-configurable sampling rate : 31.25 Hz - 31,250 Hz! |
| User-configurable recording time : 1 milliseconds to 17 minutes! |
| Recording and saving of the raw data (keep the integrity of the recordings). No filtering. |
| Use of Shunts NOT required to measure the current. |
| DIGITAL OUTPUTS/COMMAND OUTPUTS |
| Unlimited numbers of programmable commands (user-configurable) available such as : Open (O), Close (C), O-C, C-O, O-C-O, C-O-C-O, etc. |
| Pulse width : 0 to 2,000 ms, with millisecond precision |
| Pulse delay : 0 to 2,000 ms, with millisecond precision |
| DISPLAY OF THE RESULTS |
| Instantaneous display of the results (graphical and tabular reports) through a color computer screen |
| All graphics reports are printable, even after scaling, zooming, etc. |
| ADDITIONAL CAPABILITIES |
| Capability of doing on-line testing of breaker's First-trip |
| Capability of doing on-line monitoring |
| Capability of doing dynamic contact resistance measurement |
| ENVIRONMENTS |
| Environment : 0 to 50. C in any voltage environment (up to 800 kV) |
| Humidity : 0-95% Non Con. |
| Power : 240V-50Hz / 120V-60Hz |
| Auto-portable unit (no extra carrying/transport case required) |
| INTERNATIONAL STANDARDS |
| Conducted emission EN 55011 : 19991, CLASS A |
| Radiated emission EN 55011 : 1991, CLASS A |
| RF Immunity EN 61000-4-3 :1997 & ENV 50204 : 1996, 10 V/m |
| Conducted Immunity EN 61000-4-6 : 1996, 10 V |
| Electrostatic Discharges EN 61000-4-2 : 1995, 8 kV/4 kV contact |
| Electrical Fast Transients EN 61000-4-4 : 1995, 2 kV |
| Zensol is accredited ISO 9001 |
| DIMENSION & WEIGHT | |||
| Size : | Small: | Medium: | Large: |
| Length: | 13" (33 cm.) | 17" (43 cm.) | 18" (46 cm.) |
| Width: | 13.5" (35 cm.) | 16.5" (42 cm.) | 19" (48 cm.) |
| Height: | 7" (18 cm.) | 10" (25.4 cm.) | 8.9" (22.6 cm.) |
| Weight: | 18.6 lb (8.45 kg) | 29 lb (13 kg) | 38 lb (17 kg) |
|
SOFTWARE SPECIFICATIONS |
| GENERAL SPECIFICATIONS |
| The units are controlled by the CBA WIN™ software through any standard PC computer. The CBA WIN™ software is supplied with the unit at no extra charge. |
| Two levels of operation: standard & advanced |
| TRUE computerized circuit breaker analyzer |
| The software initiates the commands. No external manipulation (switch or button) required to initiate the command. No test plan transfer to the unit required before test. |
| A SIMPLE CLICK OF THE MOUSE FOR ALL YOUR BREAKER TESTING |
| Recording and saving of RAW DATA (keep the integrity of the data). No filtering. |
| COMMUNICATION LINK |
| The communications between the CBA-32P and the software are done by a high speed (57 600 baud) fiber optic communication link including a RS-232 fiber optic module, a 10 feet fiber optic cable and a power cable (all supplied with the equipment at no extra charge.) |
| High speed fiber optic link: 57 600 baud |
| Extra long fiber optic cable available for maximum comfort & security (200 feet) |
| STANDARD FEATURES |
| Default file (plan test) working on any type of breakers to be tested (no specific set-up of the equipment required before the test) |
| Library of standard test plans available in the software |
| Library of standard data files available in the software |
| Library of standard graphic reports |
| Library of standard tabular reports |
| All information, as well as graphic and tabular reports, are automatically time-tagged |
| All functions are menu-driven |
| Assistant mode for easy plan tests configuration |
| Easy identification of each test |
| Possibility of introducing different and specific warnings for each command |
| Possibility of introducing specific notes on each test that will appear in the tabular report |
| Integrated communication test link |
| Integrated test leads |
| GRAPHICAL REPORTS |
| Instantaneous display of the graphics on the computer screen |
| Excellent timing diagrams : The display of the contacts on screen, as well as during the printing process, are defined very clear and precise fine lines (user-configurable colors for each signal). |
| Precise analysis of the graphic reports thanks to the graphic reports tools such as zooming, scaling, superimposing graphs for comparison, etc. |
| Up to 26 signals can be displayed on one graph |
| 10 user configurable graphics page available per command |
| GRAPHICAL TOOLS |
| Zooming |
| Scaling |
| Superimposing |
| Zooming of contact bouncing |
| TABULAR TOOLS |
| Instantaneous display of the tabular reports on the computer screen |
| Tabular reports can be designed in any language |
| TABULAR TOOL REPORTS |
| Minimum and Maximum comparison |
| Pass/Fail indicator |
| Possibility to introduce notes at the end of the tabular reports specific of each test |
| EXPORT CAPABILITIES (OPEN SOFTWARE ARCHITECTURE) |
| TEST DATA exportable to EXCEL instantaneously |
| Test plans exportable under WORD |
| Graphic exportable under Word and any word processor software |
| Tabular reports exportable as plain text or web page |
| TEST DATA transferable via fax/Modem instantaneously |
| TEST DATA exportable to customer's own maintenance exploitation system (on request) |
| IMPORT CAPABILITIES (OPEN SOFTWARE ARCHITECTURE) |
| TEST DATA import as text documents |
| Test plan import as text document |
| MEMORY CAPACITY |
| The memory and data retention are unlimited as the CBA-32P is driven by a standard computer. Consequently the capacity will actually be equal to the capacity of your computer hard disk. |
| Ability to create an extensive «virtual library» of tests and test configurations using the simple windows explorer |
| CALCULATION FUNCTIONS |
| More than 40 calculation functions are available in the software. The user can apply any of these calculation functions to the recorded signals during the tests. |
| Also, as it is the RAW DATA which are saved, new calculation functions can be applied to the signals, even months after the tests have been performed. |
| Dynamic variables per test plan: 8640 |
| Static variables: 2500 |
| Examples of some of the calculation functions: Total travel, velocity, contact wipe, over travel, rebound, Min/Max for currents and displacements, etc. |
| ADVANCED FEATURES |
| Easy User configurable tabular report designer module: The user can create its own tabular reports in any language (English, French, Spanish, German, etc.) |
| User configurable graphic report designer module: The advanced user can create its own graphic reports. |
| Automatic calculation designer module: The advanced user can create its own calculation functions and calculation files. |
| Batch testing module: The unit can perform unlimited (thousands of tests if required), automated, long and repetitive sequences of operations (such as close-open) without any operator intervention. |
| Data processing areas: Those areas are reserved to apply some mathematical functions to a signal. ex : calculation of the derivative of a signal to display the instantaneous velocity of a signal. |
| PRICES INCLUDE: |
|
| OPTIONS AND OTHER ACCESSORIES |
|
Specifications can vary without any previous notice.