On-Load Tap Changer (OLTC) Analyzer TAP-4 |
Zensol introduces a new instrument, the TAP-4 totally dedicated
to Acoustic Vibrations measurements on On-Load Tap Changers.
Faults associated to On-Load Tap Changers are at the origin of
up to 40% of the transformer failures.
This new instrument allows the maintenance crew to detect most
of common OLTC malfunctions as contact wear, arcing in diverter,
arcing in selector, synchronism problem, drive mechanism
problem, brake failure etc..
The Tap-4 is used in conjunction with accelerometers (3 maximum)
and a current sensor clamp. Its High Sampling Frequency of at
least 100 KHz allows to record a large variety of mechanical and
arcing problems.
The Tap-4 comes with powerful and user-friendly software CBV WIN
Tap to record and analyze events the OLTC events.
It integrates many calculation and graphic functions to be able
to build tests references and tests recordings for comparison
analysis.
|
Specifications
and appearance may change without notice
PDF BROCHURE
|
|
|
Main advantages |
- Testing time is short because the transformer is On-Line
- Easy installation of accelerometers and current sensors
- Could be used as a diagnostic tool to select through a large
number of transformers which ones will be candidates for a
complete inspection
- Easy detection of mechanical OLTC problems
- Robust, Light and Portable
- For use in High Voltage environment
- Can be used on any type of transformers
|
|
|
Accessories included with the instrument |
|
Technical
features |
- CBV WIN Tap software
- USB to fiber optic module
- Manual
- 1 day training at Zensol's premises (travel expenses of the
attendees not included).
|
- 3 Accelerometers inputs:
. Accelerometer sensor type : ICP
. Sensitivity : 100 mV/g
. Measurement range : +/- 50g
. Frequency range : 5 to 15000Hz
. Constant current excitation 2 to 20 mA
- 1 current input
- Sampling Frequency : 100 KHz
- Sampling time : 10 microseconds
- Recording time : unlimited
- Data Acquisition system with 16 bit resolution for A/D
conversion
|
|
|
Options |
|
- Calibration tools
- Accelerometers
- BNC to 1032 cables (3’)
- BNC-BNC cables (10’ to 50’)
- Carrying cases
|
|